Delta GES-DPS-160K
Delta GES-DPS-160K
Qty
Shipping
In about 1 week|Shipped by manufacturer|Deppon Logistics
湖塘, Wujin District, Changzhou, Jiangsu
Est. Shipping
Select a delivery region to check shipping cost
Service
Warranty 1 year/3 years, provided by the supplier warranty; using Debang, Jingdong's cross-logistics carrier, the original factory direct delivery and distribution.
Favorite
Contact Us24/7 Support

Scan to contact our customer service
For more details,
call us: 400-6611-323
call us: 400-6611-323
Overview

Specifications
Delta GES-DPS-160K output
| Output power capacity | 144KW/160KVA |
| Rated output voltage | 380/220Vac(3 phase 4 wire + G) |
| output voltage distortion | ≤ 1% |
| Output frequency (synchronized with main frequency) | 50/60 +/-0.05Hz (internal oscillator) |
| voltage stability | 1% |
| Overload capacity | ≤ 125%:10 minutes; ≤ 150%:1 minute |
Delta GES-DPS-160K input
| Rated input voltage | 380/220Vac(3 phase 4 wire + G) |
| Input frequency | 50/60 +/-5Hz |
| Operating voltage range | -40% ~ 20%(242~477/140 ~ 276Vac)* |
| current harmonic distortion | <3% |
| power factor | <0.99% |
Delta GES-DPS-160K Battery and Running Time
| Rated battery voltage | +/-240Vdc |
| Charging voltage | +/-272Vdc (adjustment range: 254 to 291Vdc) |
Delta GES-DPS-160K physical indicators
| High | 1950.00mm |
| Wide | 850.00mm |
| Deep | 865.00mm |
| Net weight | 697KG |
Delta GES-DPS-160K Environment
| Working environment | 0 - 40°C |
| Working relative humidity | 95% (no condensation) |
| Audible noise 1 m from equipment surface | <65dBA |
| IP protection level | IP20 |
Delta GES-DPS-160K Interface
| Standard type | RS232 × 1,SNMP slot × 2, dry contact output × 6, dry contact input × 2, battery cabinet temperature × 4, battery cabinet state detection × 1, parallel port × 2,REPO × 1 |
| Manage attachments | SNMP card, Modbus card, relay I/O control card, environmental monitor, SNMP hub, battery cabinet temperature sensor, battery cabinet status detection cable |
Delta GES-DPS-160K Compliance
| Safety and EMC | EN62040-1;CE;IEC61000-4;IEC62040-2 |
Delta GES-DPS-160K Display
| LED indication; "LCD graphical" display; support for multiple languages |
Other functions of Delta GES-DPS-160K
| Parallel Redundancy and Expansion | Yes (up to 8) |
| Emergency Power Off | Yes (local and remote) |
Delta GES-DPS-160K efficiency
| AC-AC | 96% |
| ECO economic model | 99% |
Installation
No data
Documents
No data